Eductor rated for optimum flow at 200 PSI (14 Bar)
Furnished with 30”(76cm) pick up tube
Variable metering valve
Removable metering valve
A large, easy to read metering dial
Ball check valve prevents back flow into foam concentrate
Operating Procedures
Must be used with a nozzle of equivalent flow rate
Maximum hose lay between eductor and nozzle on level ground using 1½"(3.8 cm) hose is 150 ft.(46m)
Maximum hose lay between eductor and nozzle on level ground using 2"(5 cm) hose is 300 ft.(91m)
Normal inlet operating pressure at eductor is 200 psi; however, the eductor can be used at lower inlet pressures with a corresponding reduction in flow rates
* Pressure loss through the Chemguard eductor is approximately 35% of the inlet pressure
Suitable
Suitable for use with water, AFFF, AR-AFFF, Fluoroprotein and Class “A” foam concentrates