The IM-10 Ten Input Monitor module provides an interface between a control panel and normally open contact devices such as pull stations, security contacts, or flow switches. The first address is set from 01 to 90 and the remaining modules are automatically assigned to the next nine higher higher addresses. Provisions are included for disabling a maximum of two unused addresses. The supervised state (normal, open or short) of the monitored device is sent back to the panel.