 Tapping Sleeves  
 
Description   Technical Data

Sample Specifications:
Ductile Iron Mechanical Joint Tapping Sleeves furnished by Kennedy Valve Company are produced in accordance with manufacturer’s standards. Chemical and physical properties of the ductile iron are in accordance with the requirements of ANSI/AWWA C110/A21.10-82.
Recess dimensions are per Manufacturer’s Standardization Society standard practice SP-60.

General Installation Instructions for Kennedy Valve MJ Tapping Sleeves:

  • Clean pipe - insert side gasket into back half of gasket grooves. Make sure ends are flush with or slightly protrude into the end gasket seating area.
  • Bolt sleeve halves together and trim side gaskets as necessary. MAKE SURE SLEEVE WILL ROTATE FREELY ON PIPE.
  • Install end gaskets, locating cut ends 90o from side gasket. If pipe is maximum OD, stretch gasket to make certain cut ends match with no gap in between.
  • Install glands and bolts – rotate sleeve to desired position. Be sure pipe is centered inside the sleeve.
  • Tighten gland bolts alternately, using 80 to 90 foot pounds.
  • After assembly, PRESSURE TEST ALL JOINTS BEFORE TAPPING. If additional tightening is required, release pressure and relax tension on gland bolts before tightening side bolts.
 