Description   Technical Data   Product Drawing

AIR-Intelligence detectors continuously adapt their sensitivity to the environment in which they are installed, providing alarm thresholds which are `relative` to the background particle levels in the protected area, instead of placing the alarm threshold at a fixed level relative to ambient conditions. 
At any time, the detector`s performance remains constant, regardless of fluctuations in the normal background particle level. AIR-Intelligence detectors only respond to particle levels significantly above the expected background level, such as from a genuine fire situation.

Features:

• High-sensitivity provided by laser-based forward light scatter mass detection and particle evaluation for reliable early warning detection.
• Four programmable alarm thresholds (Aux, Pre-Alarm, Fire 1 and Fire 2).
• ClassiFire™ Perceptive Artificial Intelligence system.
• Dual Technology LDD 3D3 Laser Dust Discrimination and Elimination system.

Technical Specifications:

Particle Sensitivity Range: 0.003 to 10 micron.

The Industry`s Widest Sensitivity Range: 0.00046 to 7.62% obs/ft.

RS-485 built-in as standard for networking and remote communications. Up to 127 detectors per loop with 4,000 ft. between devices.

RS-232 built-in for direct PC interface without the expense of high level interface equipment.

Powered by 24-Volt DC regulated supply, low current draw.

 

 